DEM041AR
kilowatt
hour meters
Three phase Four wire electronic Multi-rate Din-Rail Active Energy Meter |
|
|
DEM041AR
kilowatt hour meters
Application |
|
Model
DEM041AR three phase four wire electronic multi-rate DIN rail active
energy meter is a kind of three phase four wire
three tariffs (time-sharing billing) active energy meter, the meter
completely accord with relevant technical requirements
of class 1 three phase active energy meter stipulated in
international standard IEC 62053-21. It can accurately
and directly measure 50Hz or 60Hz active energy consumption from
three phase four wire AC electricity net. This
meter has seven digits LCD monitors shows various consumption data
and information. And there are far infrared and
RS485 communication module in it. It is use for setting and reading
the meter. Contact with all kind of AMR system conveniently.
It has following features: Good reliability, small volume, light
weight, specious nice appearance, convenient installation,
etc. This meter has already got the patent certificate from Chinese
national Intellectual Property Office at present.
Patent certificate NO. ZL 2006 3 0107349.1, any other country patent
certificate are in assessing.
|
| |
|
 |
|
|
DEM041AR
kilowatt hour meters
Function and features: |
|
-DEM041AR
kilowatt hour meters-35mm
standard DIN rail installation, complying with standard DIN EN50022.
Or front
board setting (mounting holes center
distance 63 mm), users can choose any one by
themselves.
-DEM041AR
kilowatt hour meters-Ten
pole
width (Modulus 12.5mm), complying with standard JB/T7121-1993.
-DEM041AR
kilowatt hour meters-Type S connection (Inlet from bottom, outlet from top), use CT
connect operation, may
select 27 CT ratio, the meter will
read directly after set, and needn’t multiplied by CT rate.
-DEM041AR
kilowatt hour meters-Have three tariffs, may select 12 daily period of times. You can set
the date arbitrary which
can automatically read the
meter every month. May select single tariff function in weekend.
(Please specified when ordering)
-DEM041AR
kilowatt hour meters-There
are a clock and Maintenance-free backup lithium batteries in it.
Battery capacity
detection and display all the time.
It can keep the electricity data for 12 months. The data
can be kept forever after power cut off.
-DEM041AR
kilowatt hour meters-May select cycle display (default) or push the button itemized
display, we can set the cycle
display, it can display 14 data
at most. Can select the data which displayed, Data 5+2
digits(99999.91kWh, Only when CT ratio 5:5A) or 7 digits
display.
It is choose by the CT
ratio which is set.
-DEM041AR
kilowatt hour meters-There is a polarity port of pulse output passive closed and a no
polarity port of pulse
output passive distant, the output rate
is 10kWh/ Pulse), Complying with standard IEC
62053-31 and DIN 43864.
-DEM041AR
kilowatt hour meters-There
are far infrared and a port of RS485 communication data. It is use for
setting and
reading the meter. Set and operation
have password protection, communication protelot
complying with standard DL/T645-1997.
-DEM041AR
kilowatt hour meters-Ten LED instructions respectively power state, signal of power
impulse, the direction of
the trend of load current, the state
rates just now and the data communications state.
-DEM041AR
kilowatt hour meters-Single direction three components measure three phase four wire
active power
consumption. It is nothing with direction
of
the trend of load current. Complying with
standard IEC 62053-21.
-DEM041AR
kilowatt hour meters-Standard configuration extended terminals cover, may select short
terminals cover, in
order to protect to use electricity
safely. (Product Configuration code is AS). |
|
DEM041AR
kilowatt hour meters
Technical parameters: |
| Model |
Accuracy |
Reference voltage(V) |
Current
specifications
(A) |
Starting Current |
Insulation
Performance |
| DEM041AR |
class1 |
3 x 127/220
3 x 230/400
|
CT/5A |
0.01 |
AC voltage 4kV for 1
minute,1.2/50us waveform impulse
voltage 6kV |
|
|
DEM041AR
kilowatt hour meters Outer and mount dimension: |
|
|
|
DEM041AR
kilowatt hour meters
Wiring diagram(Type S) |
|
|
|
|
|
|
|
|
| |
|
Our Products |
|
|
Watt hour meter,
watt hour meters,
kilowatt hour meter,
kilowatt hour meters,
kilowatt-hour meter,
kilowatt-hour meters,
kwhmeter,
kwh meters,
electricity meter,
electricity meters,
electric meter,
electric meters,
electronic meter,
electronic meters,
electrical meter,
electrical meters,
KwhMeters,
kwh-meter,
Electric Energy Meter,
billing meter,
Static Watt Hour Meter,
mechanical kwh meters,
watthour power meter,
AC Kilowatt-Hour Meter,
mechanical kwh meter,
mechanical energy meter,
single phase mechanical KWH meter,
three phase mechanical KWH meter,
electro-mechanical kWh meter,
prepaid KWH meter,
prepayment meter,
electricity meters with prepaid chip cards,
multi meter,
Single phase electronic prepayment watt-hour meter,
china meter, top-quality electricity meters,
DIN rail kWh meters,
din rail watt-hour meter,
DIN Rail Energy Meter,
Din-rail Electronic Watt-hour Meter,
DIN Rail Mounted kWh Meters,
single phase DIN rail watt-hour meter,
single phase DIN rail kWh meters,
three phase din rail kWh meter,
three Phase electronic kWh electricity meters,
Single Phase electronic kWh electricity meters,
Din Mount single-phase class 1 kilowatt hour meter,
Din Mount three-phase class 1 kilowatt hour meter,
Din Rail mount 1 Module single phase Kilowatt Hour Meter |
|
|
|